Installation Manual (View Online) – KHTA / KBTA / KRTA / KCTA Series (R32): Ducted Indoor ARTH24KHTA, ARTH30KHTA, ARTH36KHTA, ARTH45KHTA, ARTH54KHTA, ARTH60KHTA + Outdoor AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA + UTY-RNRT Wired Controller
Applies to:
Indoor (Ducted): ARTH24KHTA / ARTH30KHTA / ARTH36KHTA / ARTH45KHTA / ARTH54KHTA / ARTH60KHTA
Outdoor (Single type): AOTH30KBTA / AOTH36KBTA / AOTH45KBTA / AOTH54KBTA / AOTH60KBTA
Outdoor (Single type): AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA
Outdoor (Single type): AOTH45KCTA / AOTH54KCTA / AOTH60KCTA
Wall Controller (Wired): UTY-RNRT
Refrigerant: R32
Audience: Authorised service personnel / professional installers
Contents
- 1) Safety and compliance
- 2) R32 refrigerant requirements
- 3) Tools and materials (R32/R410A rated)
- 4) System overview (power, control, commissioning flow)
- 5) Refrigerant piping requirements
- 6) Electrical requirements
- 7) Outdoor unit installation (AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA)
- 8) Indoor unit installation (ARTH24KHTA, ARTH30KHTA, ARTH36KHTA, ARTH45KHTA, ARTH54KHTA, ARTH60KHTA)
- 9) Pressure test, evacuation, commissioning
- 10) Additional refrigerant charging (AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA)
- 11) Indoor function settings (ARTH – static pressure / airflow)
- 12) Test run and handover
- 13) Pump down (forced cooling operation)
- 14) Error codes (indoor/outdoor consolidated)
- 15) UTY-RNRT specific error displays
1) Safety and compliance
- Installation and servicing must be completed by qualified and experienced personnel only.
- Do not energise the system until all installation work is complete and covers are fitted.
- After isolating power, wait before touching electrical components (observe manufacturer discharge guidance).
- If refrigerant leakage occurs during works: ventilate immediately and remove ignition sources.
- Use vacuum pump evacuation (do not purge with refrigerant).
- Ensure correct grounding/earthing and earth leakage protection as required by local regulations.
2) R32 refrigerant requirements
- R32 operates at higher pressures than legacy systems; only use R32/R410A-rated tools, hoses and materials.
- Charging port thread for R32/R410A: 1/2–20 UNF.
- Prevent moisture/foreign matter entering piping; seal pipe ends during storage/handling.
- Leak detection must be suitable for flammable refrigerants; do not use open flame methods.
- Comply with relevant safety standards and local regulations for flammable refrigerants.
3) Tools and materials (R32/R410A rated)
- High-pressure gauge manifold suitable for R32/R410A
- R32/R410A charging hoses
- Vacuum pump and appropriate adapters (as required)
- R32/R410A compatible leak detector
- Tube cutter, deburr tool, flare tool suitable for R32/R410A, torque wrenches for flare nuts and caps
- Nitrogen cylinder + regulator for pressure testing
4) System overview (power, control, commissioning flow)
- Recommended workflow: Install (mechanical) → electrical → pressure test → evacuation → open service valves → add charge (if required) → function settings (static pressure) → test run → handover.
- Confirm wiring terminal numbering matches on both ends and cable routing avoids contact with refrigerant piping and sharp edges.
- Where a wired controller is used (UTY-RNRT), ensure addressing / control configuration aligns to the job scope before commissioning.
5) Refrigerant piping requirements
5.1 Copper pipe material and minimum wall thickness (R32/R410A)
- Use seamless phosphor deoxidised copper.
- Do not use existing piping (risk of contamination and incompatibility).
Minimum wall thickness (annealed copper) by pipe outside diameter:
- 6.35 mm outside diameter (nominal size 1/4"): minimum thickness 0.80 mm
- 9.52 mm outside diameter (nominal size 3/8"): minimum thickness 0.80 mm
- 12.70 mm outside diameter (nominal size 1/2"): minimum thickness 0.80 mm
- 15.88 mm outside diameter (nominal size 5/8"): minimum thickness 1.00 mm
- 19.05 mm outside diameter (nominal size 3/4"): minimum thickness 1.20 mm
5.2 Line sizes (single type – standard outdoor reference)
- Typical pipe diameter (Liquid / Gas): 9.52 mm (3/8") / 15.88 mm (5/8")
- Always insulate both liquid and gas lines. Increase insulation thickness in high humidity environments.
- Protect pipe ends against moisture/dust entry during storage and installation.
5.3 System piping limits (outdoor unit reference)
- Minimum piping length: 5 m
- Maximum height difference (Indoor → Outdoor): 30 m
- Maximum piping length by outdoor model family:
- AOTH30KBTA / AOTH36KBTA / AOTH45KBTA / AOTH54KBTA / AOTH36KRTA / AOTH45KRTA / AOTH54KRTA: 50 m
- AOTH60KBTA / AOTH60KRTA: 50 m
- AOTH45KCTA / AOTH54KCTA / AOTH60KCTA: 75 m
6) Electrical requirements
6.1 Outdoor unit power supply (AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA)
- Voltage rating: 1Φ 220–240 V (50 Hz) / 3Φ 380–415 V (50 Hz)
- Operating range: 1Φ 198–264 V / 3Φ 342–457 V
- Power supply cable (minimum):
- Single phase: Minimum 4 mm² (Type 60245 IEC 66), 2 cable + Earth (Ground)
- Three phase: Minimum 2.5 mm² (Type 60245 IEC 57), 4 cable + Earth (Ground)
Breaker capacity / Earth leakage breaker (reference) by outdoor model grouping:
- AOTH30KBTA / AOTH36KBTA (Single phase): Breaker capacity 25 A; Earth leakage breaker 30 mA
- AOTH45KBTA / AOTH54KBTA (Single phase): Breaker capacity 32 A; Earth leakage breaker 30 mA
- AOTH36KRTA / AOTH45KRTA / AOTH54KRTA (Three phase): Breaker capacity 16 A; Earth leakage breaker 30 mA
- AOTH45KBTA / AOTH54KBTA / AOTH60KBTA (Single phase): Breaker capacity 32 A; Earth leakage breaker 30 mA
- AOTH60KRTA (Three phase): Breaker capacity 16 A; Earth leakage breaker 30 mA
- Install a disconnect device with a contact gap of at least 3 mm in all poles nearby the units (indoor and outdoor) as required by local regulations.
6.2 Indoor to outdoor connection cable
- Refer to the indoor unit installation manual for connection cable specifications and terminal assignments.
- Limit voltage drop to less than 2%; increase conductor size if required.
- Do not connect AC supply to transmission terminals.
7) Outdoor unit installation (AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA)
7.1 Location and mounting
- Install on a base that can withstand weight and vibration; use anchor bolts and appropriate anti-vibration measures.
- Maintain required clearances for airflow and service access (including discharge air recirculation control).
- Do not install where combustible gas may accumulate or in corrosive environments.
- Secure appropriately for local wind/weather conditions.
7.2 Drain considerations (outdoor)
- Heating operation produces drain water; route to a suitable drain point where applicable.
- In freezing climates, apply appropriate freeze protection strategies per local best practice.
8) Indoor unit installation (ARTH24KHTA, ARTH30KHTA, ARTH36KHTA, ARTH45KHTA, ARTH54KHTA, ARTH60KHTA)
8.1 Site selection and serviceability
- Install in a location that supports the unit mass and minimises vibration transmission.
- Ensure ducting, filter access, and condensate drain access are serviceable after installation.
- Ensure appropriate access for electrical service and refrigerant piping connections.
8.2 Ductwork and airflow management (critical)
- Confirm ductwork design external static pressure (ESP) aligns with unit capability.
- Seal duct joints to prevent air leakage and performance degradation.
- Confirm return air path and filter arrangement prevents debris ingress to the fan/coil.
8.3 Condensate drain
- Provide correct fall and trapping per local best practice to prevent blow-off and odours.
- Insulate condensate line where sweating may occur.
- Water-test drainage prior to ceiling closure / handover.
9) Pressure test, evacuation, commissioning
9.1 Flare work – tightening torques (system)
Flare nut tightening torque by pipe size:
- 1/4" pipe size (outside diameter 6.35 mm): 16–18 N·m
- 3/8" pipe size (outside diameter 9.52 mm): 32–42 N·m
- 1/2" pipe size (outside diameter 12.70 mm): 49–61 N·m
- 5/8" pipe size (outside diameter 15.88 mm): 63–75 N·m
- 3/4" pipe size (outside diameter 19.05 mm): 90–110 N·m
9.2 Leak test (air tightness test)
- Perform an air tightness test using nitrogen while all outdoor unit valves are closed.
- Use the test pressure indicated on the outdoor unit nameplate and confirm all joints are leak-free prior to evacuation.
9.3 Vacuum evacuation
- Evacuate to –0.1 MPa (–76 cmHg).
- When –0.1 MPa is reached, operate the vacuum pump for at least 60 minutes.
- After evacuation, disconnect hoses, then open service valves fully and refit caps to specified torques.
9.4 Service valve / port cap torques (outdoor reference)
Service valve / port cap tightening torques:
- Blank cap (applicable sizes 1/4", 3/8"): 20–25 N·m
- Blank cap (applicable size 1/2"): 28–32 N·m
- Blank cap (applicable size 5/8"): 30–35 N·m
- Blank cap (applicable size 3/4"): 35–40 N·m
- Charging port cap (R32/R410A): 12.5–16 N·m
10) Additional refrigerant charging (AOTH30KBTA, AOTH36KBTA, AOTH45KBTA, AOTH54KBTA, AOTH60KBTA, AOTH36KRTA, AOTH45KRTA, AOTH54KRTA, AOTH60KRTA, AOTH45KCTA, AOTH54KCTA, AOTH60KCTA)
- Pre-charge length: 30 m
- If piping length exceeds 30 m, additional refrigerant is required.
- Charging guideline: 40 g per metre beyond 30 m.
- Record factory charge, additional charge, and total charge on the outdoor unit refrigerant label.
10.1 Additional charge guidance for KBTA and KRTA outdoor models
Applies to: AOTH30KBTA / AOTH36KBTA / AOTH45KBTA / AOTH54KBTA / AOTH60KBTA / AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA
- Piping length 30 m or less: No additional refrigerant required
- Piping length 40 m: Add +400 g (40 g/m beyond 30 m)
- Piping length 50 m: Add +800 g (40 g/m beyond 30 m)
- Guideline: 40 g per metre beyond 30 m
10.2 Additional charge guidance for KCTA outdoor models
Applies to: AOTH45KCTA / AOTH54KCTA / AOTH60KCTA
- Piping length 30 m or less: No additional refrigerant required
- Piping length 40 m: Add +400 g (40 g/m beyond 30 m)
- Piping length 50 m: Add +800 g (40 g/m beyond 30 m)
- Piping length 60 m: Add +1200 g (40 g/m beyond 30 m)
- Piping length 70 m: Add +1600 g (40 g/m beyond 30 m)
- Piping length 75 m: Add +1800 g (40 g/m beyond 30 m)
- Guideline: 40 g per metre beyond 30 m
10.3 Maximum total charge (per outdoor model reference)
- AOTH30KBTA / AOTH36KBTA: 2700 g (1900 g + 800 g)
- AOTH45KBTA / AOTH54KBTA: 3500 g (2700 g + 800 g)
- AOTH60KBTA / AOTH60KRTA: 4200 g (with a piping length of 50 m)
- AOTH45KCTA: 5200 g (with a piping length of 75 m)
- AOTH54KCTA / AOTH60KCTA: 5600 g (with a piping length of 75 m)
11) Indoor function settings (ARTH – static pressure / airflow)
- Purpose: Align indoor fan operation to the duct system’s design external static pressure (ESP).
- Factory setting reference: 100 Pa.
- Complete ducting and filters before setting ESP. Incomplete ductwork will produce incorrect airflow outcomes.
- Function settings are performed via the installed controller / service procedure (wired remote controller environment).
11.1 Static pressure setting (Function No. 26) – ARTH24KHTA / ARTH30KHTA / ARTH36KHTA
Static pressure setting options for Function No. 26 (ARTH24KHTA, ARTH30KHTA, ARTH36KHTA):
- Function No. 26, Setting value 06: Static pressure 60 Pa
- Function No. 26, Setting value 07: Static pressure 70 Pa
- Function No. 26, Setting value 08: Static pressure 80 Pa
- Function No. 26, Setting value 09: Static pressure 90 Pa
- Function No. 26, Setting value 10: Static pressure 100 Pa
- Function No. 26, Setting value 11: Static pressure 110 Pa
- Function No. 26, Setting value 12: Static pressure 120 Pa
- Function No. 26, Setting value 13: Static pressure 130 Pa
- Function No. 26, Setting value 14: Static pressure 140 Pa
- Function No. 26, Setting value 15: Static pressure 150 Pa
- Function No. 26, Setting value 16: Static pressure 160 Pa
- Function No. 26, Setting value 17: Static pressure 170 Pa
- Function No. 26, Setting value 18: Static pressure 180 Pa
- Function No. 26, Setting value 19: Static pressure 190 Pa
- Function No. 26, Setting value 20: Static pressure 200 Pa
- Function No. 26, Setting value 21: Static pressure 210 Pa
- Function No. 26, Setting value 31: Static pressure Standard (60 Pa)
- Function No. 26, Setting value 32: Static pressure Automatic airflow adjustment
11.2 Static pressure setting (Function No. 26) – ARTH45KHTA / ARTH54KHTA / ARTH60KHTA
Static pressure setting options for Function No. 26 (ARTH45KHTA, ARTH54KHTA, ARTH60KHTA):
- Function No. 26, Setting value 06: Static pressure 60 Pa
- Function No. 26, Setting value 07: Static pressure 70 Pa
- Function No. 26, Setting value 08: Static pressure 80 Pa
- Function No. 26, Setting value 09: Static pressure 90 Pa
- Function No. 26, Setting value 10: Static pressure 100 Pa
- Function No. 26, Setting value 11: Static pressure 110 Pa
- Function No. 26, Setting value 12: Static pressure 120 Pa
- Function No. 26, Setting value 13: Static pressure 130 Pa
- Function No. 26, Setting value 14: Static pressure 140 Pa
- Function No. 26, Setting value 15: Static pressure 150 Pa
- Function No. 26, Setting value 16: Static pressure 160 Pa
- Function No. 26, Setting value 17: Static pressure 170 Pa
- Function No. 26, Setting value 18: Static pressure 180 Pa
- Function No. 26, Setting value 19: Static pressure 190 Pa
- Function No. 26, Setting value 20: Static pressure 200 Pa
- Function No. 26, Setting value 21: Static pressure 210 Pa
- Function No. 26, Setting value 22: Static pressure 220 Pa
- Function No. 26, Setting value 23: Static pressure 230 Pa
- Function No. 26, Setting value 24: Static pressure 240 Pa
- Function No. 26, Setting value 25: Static pressure 250 Pa
- Function No. 26, Setting value 26: Static pressure 260 Pa
- Function No. 26, Setting value 31: Static pressure Standard (60 Pa)
- Function No. 26, Setting value 32: Static pressure Automatic airflow adjustment
11.3 Operational guidance (field practical)
- Manual setting: Select the required Pa value when duct design ESP is known.
- Automatic airflow adjustment: Use when commissioning requires automated fan calibration (ensure system is complete and stable before initiation).
- After changing settings, validate airflow, noise profile, and temperature performance outcomes under normal load conditions.
12) Test run and handover
12.1 Check items
- Controller operation and display status normal
- Indoor fan operation stable (no hunting / abnormal ramping)
- Airflow achieved and duct system balanced
- Drainage normal (no water leakage)
- No abnormal noise or vibration
- No refrigerant leakage detected
12.2 Customer guidance
- Explain controller operation, setpoints, timers/schedules (where applicable).
- Explain filter access/cleaning intervals and service requirements.
- Confirm any building management interface / external interlocks (if installed).
13) Pump down (forced cooling operation)
- Use pump down for relocation/disposal refrigerant recovery in accordance with the manufacturer procedure and local regulatory requirements.
- Initiate forced cooling/test run mode per controller guidance (method varies by controller type).
- Close the 2-way valve fully, then close the 3-way valve after the required run period, then stop operation.
- Do not proceed if refrigerant is depleted due to damaged piping; confirm leak-free condition first.
14) Error codes (indoor/outdoor consolidated)
Error codes may be displayed on the wired controller, or indicated via indoor LED blink patterns where applicable. Capture the code, confirm wiring/communication integrity, and follow standard diagnostic workflow.
14.1 Error code list (one-line format)
- 11 – Serial communication error
- 12 – Wired remote controller communication error
- 15 – Check run unfinished / automatic airflow adjustment error
- 16 – Peripheral unit transmission PCB connection error
- 18 – External communication error
- 21 – Unit number / address setting error (system dependent)
- 22 – Indoor unit capacity error
- 23 – Combination error
- 24 – Connection unit number error (system dependent)
- 26 – Indoor unit address setting error
- 27 – Primary/secondary unit setup error (system dependent)
- 29 – Connection unit number error in wired remote controller system
- 31 – Power supply interruption error
- 32 – Indoor unit PCB model information error
- 33 – Indoor unit motor electricity consumption detection error
- 35 – Manual auto switch error
- 39 – Indoor unit power supply error for fan motor
- 3A – Indoor unit communication circuit (wired remote controller) error
- 41 – Room temperature sensor error
- 42 – Indoor unit heat exchanger middle temperature sensor error
- 44 – Occupancy sensor error
- 51 – Indoor unit fan motor error
- 53 – Drain pump error
- 57 – Damper error
- 59 – Indoor unit fan motor 2 error
- 5U – Indoor unit error
- 61 – Outdoor unit reverse/missing phase and wiring error
- 62 – Outdoor unit main PCB model information error / communication error
- 63 – Inverter error
- 64 – Active filter error / PFC circuit error
- 65 – Trip terminal / IPM temperature error
- 68 – Rush current limiting resistor temperature rise error
- 6A – Display PCB microcomputer communication error
- 71 – Discharge temperature sensor error
- 72 – Compressor temperature sensor error
- 73 – Outdoor heat exchanger liquid temperature sensor error
- 74 – Outdoor temperature sensor error
- 75 – Suction gas temperature sensor error
- 76 – 2-way / 3-way valve temperature sensor error
- 77 – Heat sink temperature sensor error
- 82 – Sub-cool heat exchanger sensor error
- 83 – Liquid pipe temperature sensor error
- 84 – Current sensor error
- 86 – Pressure sensor / high pressure switch error
- 94 – Trip detection
- 95 – Compressor rotor position detection error (permanent stop)
- 97 – Outdoor unit fan motor 1 error
- 98 – Outdoor unit fan motor 2 error
- 99 – 4-way valve error
- 9A – Expansion valve (coil) error
- A1 – Discharge temperature error
- A3 – Compressor temperature error
- A4 – High pressure error
- A5 – Low pressure error
- AC – Heat sink temperature error
- J2 – Branch boxes error (system dependent)
15) UTY-RNRT specific error displays
These error displays are specific to UTY-RNRT wired remote controller system conditions (in addition to the consolidated system error code list above).
15.1 UTY-RNRT error display list (one-line format)
- CC.1 – Sensor error (wired remote controller side)
- C2.1 – Transmission PCB error
- 12.1 – Wired remote controller communication error
- 12.3 – Communication circuit error (wired remote controller)
- 12.4 – Indoor unit communication circuit error (wired remote controller)
- 26.4 – Wired remote controller unit number or refrigerant circuit address setting error
- 26.5 – Indoor unit address setting error
- 15.4 – Data acquisition error
Document control: This Solution article is intended as a consolidated, text-only field reference for KHTA/KBTA/KRTA/KCTA ducted installation and commissioning. Always comply with local regulations and manufacturer requirements for detailed diagrams, part numbers, and regional variations.