AIRSTAGE Roof Top Packaged Units (RTPU) – RAQ Series (Single Skin)

Applies to:
Standard Single Skin (Radial Fan): RAQ/K/WP 15 / 17 / 110 / 112 / 115 / 118 / 224 / 230 / 236
Premium Single Skin (EC Inverter Plug Fan):  Premium 110, Premium 112, Premium 115, Premium 118, Premium 224, Premium 230, Premium 236, RAQKWPEC110, RAQKWPEC112, RAQKWPEC115, RAQKWPEC118, RAQKWPEC224, RAQKWPEC230, RAQKWPEC236 


Contents


1) Overview and key features

  • Product type: Single Skin Roof Top Packaged Units (RTPU)
  • Standard range: Scroll compressors + radial fan
  • Premium range: Scroll compressors + EC inverter plug fan
  • Power supply: 400V / 50Hz
  • Air treatment: Full recirculation; economiser option available

2) Standard Single Skin specifications (RAQ/K/WP)

Models: 15 / 17 / 110 / 112 / 115 / 118 / 224 / 230 / 236

ParameterUnit1517110112115118224230236
Cooling performance (AS/NZS 3823.1.2)
Cooling capacity (1)TON3.85.16.99.010.312.317.219.625.4
Cooling capacity (1)kW13.317.924.431.736.143.360.568.889.4
Absorbed power (1)kW4.25.67.810.111.514.820.723.430.7
EER (1)-3.173.203.133.143.142.932.922.942.91
Heating performance (AS/NZS 3823.1.2)
Heating capacity (2)TON3.85.37.19.110.312.417.920.426.0
Heating capacity (2)kW13.518.524.832.136.243.663.071.691.6
Absorbed power (2)kW4.25.57.79.811.013.420.122.328.3
COP (2)-3.213.363.223.283.293.253.133.213.24
Air treatment section
Airflowcfm182119912648334640034998667283249997
Airflowm³/s0.860.941.251.581.892.363.153.934.72
Available static pressurein WG0.240.240.600.600.600.600.840.840.84
Available static pressurePa6060150150150150210210210
Fans111111111
Filters--G4G4G4G4G4G4G4G4
Condensing section
Airflowcfm396138346036588894049404188291882918829
Airflowm³/s1.871.812.852.784.444.448.898.898.89
Compressors111111222
Refrigerant circuits111111222
Capacity steps%0-1000-1000-1000-1000-1000-1000-50-1000-50-1000-50-100
Acoustics
Sound pressure – STD version (3)dB(A)666665666770717271
Sound pressure – SL accessory (3)dB(A)636362636467686968
Weights and dimensions
Transport weightkg480525570655670770113011901295
Operating weightkg465510555640655755111511751280
Length (L)mm120014501600180020002140210022102330
Width (W)mm120013001200145014501750190019001900
Height (H)mm118012101425142514301490197019702325

3) Premium Single Skin specifications (RAQ/K/WP/EC)

Models: 15 / 17 / 110 / 112 / 115 / 118 / 224 / 230 / 236

ParameterUnit1517110112115118224230236
Cooling performance (AS/NZS 3823.1.2)
Cooling capacity (1)TON3.95.17.09.010.312.317.219.625.7
Cooling capacity (1)kW13.618.124.531.836.243.460.668.990.4
Absorbed power (1)kW3.95.47.710.011.414.720.623.329.7
EER (1)-3.493.353.183.183.182.952.942.963.04
Heating performance (AS/NZS 3823.1.2)
Heating capacity (2)TON3.95.37.19.210.312.417.920.426.3
Heating capacity (2)kW13.818.724.932.236.343.763.171.792.6
Absorbed power (2)kW3.95.37.69.710.913.320.022.227.3
COP (2)-3.543.533.283.323.333.293.163.233.39
Air treatment section
Airflowcfm182119912648334640034998667283249997
Airflowm³/s0.860.941.251.581.892.363.153.934.72
Available static pressurein WG0.240.240.600.600.600.600.840.840.84
Available static pressurePa6060150150150150210210210
Fans111111111
Filters--G4G4G4G4G4G4G4G4
Condensing section
Airflowcfm396138346036588894049404188291882918829
Airflowm³/s1.871.812.852.784.444.448.898.898.89
Compressors111111222
Refrigerant circuits111111222
Capacity steps%0-1000-1000-1000-1000-1000-1000-50-1000-50-1000-50-100
Acoustics
Sound pressure – EC version (3)dB(A)666665666770717271
Sound pressure – SL accessory (3)dB(A)636362636467686968
Weights and dimensions
Transport weightkg495560610695715820121012701415
Operating weightkg480545595680700805119512551400
Length (L)mm120014501600180020002140210022102330
Width (W)mm120013001200145014501750190019001900
Height (H)mm118012101425142514301490197019702325

4) Electrical – power supply cable sizing (by model)

Purpose: The table below provides the power supply cable sizing per model (recommended cross-section and maximum protection rating), aligned with the RAQ electrical diagrams provided. Final selection must also consider installation method, derating, grouping, and voltage drop in accordance with applicable standards.

ModelRecommended power supply cable size cross-sectionMax circuit breaker
RAQ110
Premium 110
RAQKWPEC110
6 mm² + 6 mm² (PE)25 A
RAQ112
Premium 112
RAQKWPEC112
6 mm² + 6 mm² (PE)32 A
RAQ115
Premium 115
RAQKWPEC115
6 mm² + 6 mm² (PE)40 A
RAQ118
Premium 118
RAQKWPEC118
10 mm² + 10 mm² (PE)50 A
RAQ224
Premium 224
RAQKWPEC224
16 mm² + 16 mm² (PE)63 A
RAQ230
Premium 230
RAQKWPEC230
25 mm² + 16 mm² (PE)80 A
RAQ236
Premium 236
RAQKWPEC236
35 mm² + 16 mm² (PE)100 A

Note: Cable sizing for RAQ15 / RAQ17 is not included in the RAQ110–RAQ236 electrical drawing set supplied with this solution. Confirm via the unit-specific wiring diagram and unit nameplate data.


5) Weights and dimensions (quick reference)

Objective: Use this section for lift planning, structural coordination, and logistics. Confirm final lifting points and mass on the unit prior to rigging.

ModelTransport (kg)Operating (kg)Dimensions (L × W × H) mm
RAQ154804651200 × 1200 × 1180
RAQ175255101450 × 1300 × 1210
RAQ110
Premium 110
RAQKWPEC110
5705551600 × 1200 × 1425
RAQ112
Premium 112
RAQKWPEC112
6556401800 × 1450 × 1425
RAQ115
Premium 115
RAQKWPEC115
6706552000 × 1450 × 1430
RAQ118
Premium 118
RAQKWPEC118
7707552140 × 1750 × 1490
RAQ224
Premium 224
RAQKWPEC224
113011152100 × 1900 × 1970
RAQ230
Premium 230
RAQKWPEC230
119011752210 × 1900 × 1970
RAQ236
Premium 236
RAQKWPEC236
129512802330 × 1900 × 2325

6) Ratings and measurement notes

  • Cooling rating condition (1): Evaporator inlet air temperature 27°C d.b. / 19°C w.b.; ambient air temperature 35°C.
  • Heating rating condition (2): Condenser inlet air temperature 20°C; ambient air temperature 7°C d.b. / 6°C w.b.
  • Sound pressure (3): Measured in free field conditions at 1 m from the unit, in accordance with ISO 3744.
  • Service clearance: Allow minimum 1000 mm clearance at the electrical board side for service access.