Applies to (as covered by attached manuals):
Indoor (Ducted): ARTH18KMTAP / ARTH24KMTAP / ARTH30KMTAP / ARTH36KMTAP / ARTH45KMTAP / ARTH54KMTAP
Outdoor (Single type): AOTH30KBTA / AOTH36KBTA / AOTH45KBTA / AOTH54KBTA
Outdoor (Single type): AOTH24KCTA / AOTH30KCTA
Wall Controller (Wired): UTY-RNRT (UI / error-display guidance aligned to UTY-RNR family)
Optional parts referenced: Air filter kit UTD-LFDA / UTD-LFDB
Refrigerant: R32
Audience: Authorised service personnel / professional installers
Contents
1) Safety and compliance
- Installation, electrical work, and commissioning must be performed by qualified and experienced personnel in accordance with applicable standards and local regulations.
- Do not energise the system until all installation work is complete, covers are fitted, and terminals are verified correct and secure.
- After isolating power, wait for component discharge before touching electrical parts.
- If refrigerant leakage occurs during works: ventilate immediately, remove ignition sources, and implement spill/leak response procedures suitable for A2L refrigerants.
- Use vacuum pump evacuation; do not purge with refrigerant.
- Ensure correct grounding/earthing, appropriate overcurrent protection, and earth leakage protection as required by local regulations.
- Do not touch aluminium heat exchanger fins; handle equipment to prevent sharp-edge injury and property damage.
2) R32 refrigerant requirements
- R32 is an A2L refrigerant (mildly flammable). Implement ignition control, adequate ventilation, and leak detection practices consistent with flammable refrigerant requirements.
- R32 operates at higher pressures than legacy refrigerants. Use only R32/R410A-rated tools, hoses, and materials.
- Charging port thread for R32/R410A service ports: 1/2–20 UNF.
- Prevent moisture/foreign matter entering piping; cap/seal pipe ends during storage/handling and between process steps.
- Leak detection must be suitable for flammable refrigerants; do not use open flame methods.
- Use approved recovery methods and cylinders for refrigerant removal, relocation, or end-of-life service activities.
- High-pressure gauge manifold suitable for R32/R410A
- R32/R410A charging hoses (compatible seals and pressure rating)
- Vacuum pump (recommended with check valve) and appropriate adapters
- Electronic refrigerant scale (for accurate charging by mass)
- R32/R410A compatible leak detector (A2L suitable)
- Tube cutter, deburr tool, flare tool suitable for R32/R410A, flare gauge (as required)
- Torque wrenches for flare nuts, service valves, and caps
- Nitrogen cylinder + regulator (for pressure testing / strength & tightness test)
- Insulation (liquid and gas), UV/impact protection where exposed, and sealing putty for penetrations
4) System overview (power, control, commissioning flow)
4.1 Power and control architecture (typical)
- Outdoor unit: Main supply connected to the outdoor unit disconnect/isolator.
- Indoor unit: Powered and controlled per model wiring design (verify terminals and interconnect design for the job). Do not connect AC supply to transmission terminals.
- Wired controller (UTY-RNRT): Connect to indoor controller terminals per indoor wiring diagram. Observe polarity requirements if specified by the indoor unit (many Fujitsu wired controllers are non-polar on the communication pair, however you must follow the indoor unit terminal marking).
4.2 Recommended commissioning workflow (governance flow)
- Mechanical installation complete (mounting, duct/drain, piping run, insulation)
- Electrical installation complete (power, interconnect, controller wiring, terminations verified)
- Pressure test (nitrogen) with outdoor service valves closed
- Evacuation (vacuum) to required level and hold test
- Open service valves fully, refit caps to torque
- Additional charge if piping exceeds pre-charge length
- Indoor function settings (static pressure / control features)
- Test run and validation checks
- Handover and documentation completion
4.3 Controller & service interaction (operational controls)
- Use controller Status / Error Information to capture fault codes and unit address where applicable.
- Where outdoor display PCB is fitted, use the display unit buttons to view local settings and error display modes.
- For group control / multiple controller configurations, ensure addressing and system architecture is confirmed prior to commissioning (avoid duplicated addressing / mis-termination).
5) Refrigerant piping requirements
5.1 Copper pipe material and minimum wall thickness (R32/R410A)
- Use seamless phosphor deoxidised copper appropriate for R32/R410A applications.
- Do not reuse existing piping unless it is verified suitable for R32/R410A cleanliness, pressure rating, and condition (best practice: replace).
| Outside diameter | Nominal size | Minimum thickness (annealed copper) |
|---|
| 6.35 mm | 1/4" | 0.80 mm |
| 9.52 mm | 3/8" | 0.80 mm |
| 12.70 mm | 1/2" | 0.80 mm |
| 15.88 mm | 5/8" | 1.00 mm |
| 19.05 mm | 3/4" | 1.20 mm |
5.2 Line sizes (job verification)
- Verify the correct liquid and gas line sizes on the outdoor/indoor connection specifications for the exact model combination.
- Always insulate both liquid and gas lines. Increase insulation thickness in high humidity environments to prevent sweating.
- Protect pipe ends against moisture/dust entry during storage and installation.
5.3 Piping length limits (outdoor unit reference)
- Minimum piping length: 5 m
- Maximum height difference (Indoor → Outdoor): 30 m
- Maximum piping length (by outdoor series):
- KBTA (AOTH30/36/45/54): 50 m
- KCTA (AOTH24/30): follow model limits as specified for the KCTA series (installation must comply with the permissible length table for the exact model).
6) Electrical requirements
6.1 Outdoor unit power supply (AOTH)
- Voltage rating (model dependent): 1Φ 220–240 V (50 Hz) / 3Φ 380–415 V (50 Hz)
- Operating range: 1Φ 198–264 V / 3Φ 342–457 V
- Power supply cable (minimum reference):
- Single phase: Min. 4 mm² (Type 60245 IEC 66), 2 cable + Earth (Ground)
- Three phase: Min. 2.5 mm² (Type 60245 IEC 57), 4 cable + Earth (Ground)
- Breaker capacity / Earth leakage breaker (reference set): Select per model nameplate and local code; ensure adequate interrupt capacity and leakage protection as required.
- Install a disconnect device with a contact gap of at least 3 mm in all poles nearby the units (indoor and outdoor) as required by local regulations.
6.2 Indoor to outdoor connection cable
- Follow indoor unit wiring diagram for terminal assignments and conductor sizing.
- Limit voltage drop to less than 2%; increase conductor size if required.
- Do not connect AC supply to transmission terminals.
6.3 Wired controller (UTY-RNRT) wiring governance
- Route controller cable separately from mains power to reduce noise pickup and prevent nuisance communication faults.
- Terminate securely and confirm strain relief and cable protection at entry points.
7) Outdoor unit installation
7.1 Location and mounting
- Install on a base that can withstand weight and vibration; use anchor bolts and appropriate anti-vibration measures.
- Maintain required clearances for airflow and service access. Prevent discharge air recirculation.
- Do not install where combustible gas may accumulate or in corrosive environments.
- Secure appropriately for local wind/weather conditions.
7.2 Drain considerations (outdoor)
- Heating operation produces drain water; route to a suitable drain point where applicable.
- In freezing climates, apply appropriate freeze protection strategies per local best practice.
7.3 Outdoor display unit & buttons (operation / settings / error access)
| Button | Function |
|---|
| MODE (S134) | Switch between Local setting and Error code display. |
| SELECT (S133) | Navigate individual local settings and error displays. |
| ENTER (S132) | Confirm/commit the selected local setting or error display. |
| EXIT (S131) | Return to operation status display. |
| PUMP DOWN (S130) | Start pump down operation (forced recovery sequence). |
7.4 Outdoor field settings (typical functions)
- Low noise mode: Configure via Local setting mode. Select and confirm the Low Noise mode level required for the site conditions.
- Peak cut: Configure via Local setting mode. Select the appropriate peak cut level where required by the electrical design / demand strategy.
- Auto restart: Configure as required by the job scope (power recovery behaviour).
- Governance note: Perform outdoor field settings after the indoor unit has stopped and prior to commissioning validation.
7.5 External input and output (integration readiness)
- External input can be used for interlocks and control strategies (job specific). Ensure correct signal type and wiring method.
- External output can be configured for status outputs (operation status, error status, fresh air control, auxiliary heater, etc.) where supported by the indoor unit configuration.
8) Indoor unit installation
8.1 Site selection and serviceability
- Install in a location that supports the unit mass and minimises vibration transmission.
- Ensure ducting, filter access, and condensate drain access are serviceable after installation.
- Ensure appropriate access for electrical service and refrigerant piping connections.
8.2 Ductwork and airflow management (critical)
- Confirm ductwork design external static pressure (ESP) aligns with unit capability and commissioning method.
- Seal duct joints to prevent air leakage and performance degradation.
- Confirm return air path and filter arrangement prevents debris ingress to the fan/coil.
8.3 Condensate drain
- Provide correct fall and trapping per local best practice to prevent blow-off and odours.
- Insulate condensate line where sweating may occur.
- Water-test drainage prior to ceiling closure / handover.
8.4 Optional part reference – Air filter kit (UTD-LFDA / UTD-LFDB)
- Bundle the two air filters together with the supplied cable tie (medium). The side bound with the cable tie is the bottom; the side with “PUSH” markings is the front.
- Fit each air filter to the 4 hooks on the indoor unit.
- After installation, configure the filter sign function setting as required (see Section 11).
9) Pressure test, evacuation, commissioning
9.1 Flare work – tightening torques (system)
| Pipe size | Outside diameter | Flare nut tightening torque |
|---|
| 1/4" | 6.35 mm | 16–18 N·m |
| 3/8" | 9.52 mm | 32–42 N·m |
| 1/2" | 12.70 mm | 49–61 N·m |
| 5/8" | 15.88 mm | 63–75 N·m |
| 3/4" | 19.05 mm | 90–110 N·m |
9.2 Leak test (air tightness test)
- Perform an air tightness test using nitrogen while all outdoor unit valves are closed.
- Use a test pressure suitable for the equipment and do not exceed the value specified on the outdoor unit nameplate.
- Confirm all joints are leak-free prior to evacuation.
9.3 Vacuum evacuation
- Evacuate to –0.1 MPa (–76 cmHg).
- When –0.1 MPa is reached, operate the vacuum pump for at least 60 minutes.
- Perform a vacuum hold test to confirm no moisture/air ingress (pressure rise indicates leak or moisture).
9.4 Service valve / port cap torques (outdoor reference)
| Cap / Port | Applicable sizes | Tightening torque |
|---|
| Blank cap | 1/4", 3/8" | 20–25 N·m |
| Blank cap | 1/2" | 28–32 N·m |
| Blank cap | 5/8" | 30–35 N·m |
| Blank cap | 3/4" | 35–40 N·m |
| Charging port cap | R32/R410A | 12.5–16 N·m |
9.5 Final commissioning checks
- Open service valves fully after evacuation and before starting operation.
- Confirm correct power supply, correct interconnect wiring, correct controller wiring, and secure terminals.
- Confirm drainage is normal (water test) and insulation complete.
- Confirm no refrigerant leakage using an A2L compatible electronic leak detector.
10) Additional refrigerant charging
- Pre-charge length: 30 m
- If piping length exceeds 30 m, additional refrigerant is required.
- Charging guideline: 40 g/m beyond 30 m.
- Calculation: Additional charge (g) = (Actual piping length (m) – 30) × 40, for lengths > 30 m.
- Record factory (base) charge, additional charge, and total charge on the outdoor unit refrigerant label.
10.1 KBTA (AOTH30/36/45/54)
| Piping length | Additional charge | Guideline |
|---|
| ≤ 30 m | None | 40 g/m beyond 30 m |
| 40 m | +400 g |
| 50 m | +800 g |
10.2 KCTA (AOTH24/30)
| Piping length | Additional charge | Guideline |
|---|
| ≤ 30 m | None | 40 g/m beyond 30 m |
| 40 m | +400 g |
| 50 m | +800 g |
| 60 m | +1200 g |
| 70 m | +1600 g |
| 75 m | +1800 g |
11) Indoor function settings
11.1 Governance notes
- Function settings change indoor unit control behaviour. Incorrect settings can cause malfunction, noise, water leakage, or comfort issues.
- After completing Function Setting, turn power off and back on to apply the settings.
- Record all changes in job documentation for service governance.
11.2 Setting record (functions used in this series)
- Function numbers commonly used for this ducted series include: 11 (Filter sign), 26 (Static pressure), 30/31 (Room temp control – indoor sensor cooling/heating), 35/36 (Room temp control – wired controller sensor cooling/heating), 40 (Auto restart), 42 (Room temp sensor switching), 43 (Cold air prevention), 46 (External input control), 48 (Room temp sensor switching (Aux.)), 49 (Indoor fan control for energy saving for cooling), 60 (External output function switching).
11.3 Static pressure setting (Function No. 26) – commissioning control
- Manual setting: Select the required Pa value where duct ESP is known.
- Automatic airflow adjustment: Use when commissioning requires automated fan calibration (ensure system complete and stable before initiation; not suitable where a booster fan is installed between ducts).
| Function No. | Setting value | Static pressure / mode |
|---|
| 26 | 05 | 50 Pa |
| 26 | 06 | 60 Pa |
| 26 | 07 | 70 Pa |
| 26 | 08 | 80 Pa |
| 26 | 09 | 90 Pa |
| 26 | 10 | 100 Pa |
| 26 | 11 | 110 Pa |
| 26 | 12 | 120 Pa |
| 26 | 13 | 130 Pa |
| 26 | 14 | 140 Pa |
| 26 | 15 | 150 Pa |
| 26 | 32 | Automatic airflow adjustment |
11.4 Indoor fan control for energy saving for cooling (Function No. 49)
| Function No. | Setting value | Description |
|---|
| 49 | 00 | Disable – when outdoor unit is stopped, indoor fan operates continuously following remote controller setting. |
| 49 | 01 | Enable – when outdoor unit is stopped, indoor fan operates intermittently at very low speed. |
| 49 | 02 | Remote controller – enable/disable via remote controller setting (if supported by controller type). |
11.5 External output function switching (Function No. 60)
| Function No. | Setting value | Output function |
|---|
| 60 | 00 | Operation status |
| 60 | 09 | Error status |
| 60 | 10 | Fresh air control |
| 60 | 11 | Auxiliary heater |
12) Test run and handover
12.1 Pre-test run check items
- Controller operation and display status normal
- Indoor fan operation stable (no hunting / abnormal ramping)
- Airflow achieved and duct system balanced
- Drainage normal (no water leakage)
- No abnormal noise or vibration
- No refrigerant leakage detected
12.2 Customer guidance (handover governance)
- Explain controller operation, setpoints, timers/schedules (where applicable).
- Explain filter access/cleaning intervals and service requirements.
- Confirm any building management interface / external interlocks (if installed).
- Provide commissioning records, wiring schematics as installed, and refrigerant charge documentation.
13) Pump down (forced cooling operation)
- Use pump down for relocation/disposal refrigerant recovery in accordance with manufacturer procedure and local regulatory requirements.
- Initiate forced cooling / test run mode per controller guidance (method varies by controller type).
- Close the 2-way valve fully, then close the 3-way valve after the required run period, then stop operation.
- Do not proceed if refrigerant is depleted due to damaged piping; confirm leak-free condition first.
- Use the outdoor display unit PUMP DOWN button where provided to start the pump down operation sequence.
14) Error codes (indoor/outdoor consolidated)
Error codes may be displayed on the wired controller, or indicated via outdoor display unit error mode where fitted. Capture the code, confirm wiring/communication integrity, and follow standard diagnostic workflow (power, comms, sensors, loads, then control PCB).
| Error code | Description (summary) |
|---|
| 11 | Serial communication error |
| 12 | Wired remote controller communication error |
| 15 | Check run unfinished / automatic airflow adjustment error |
| 16 | Peripheral unit transmission PCB connection error |
| 18 | External communication error |
| 21 | Unit number / address setting error (system dependent) |
| 22 | Indoor unit capacity / combination error (system dependent) |
| 23 | Communication circuit error (system dependent) |
| 24 | Indoor fan motor error |
| 25 | Drain / float switch error |
| 26 | Indoor heat exchanger temperature sensor error |
| 27 | Indoor room temperature sensor error |
| 28 | Indoor coil inlet / outlet sensor error (model dependent) |
| 29 | Indoor discharge air temperature sensor error (model dependent) |
| 2A | Outdoor unit combination error (system dependent) |
| 2C | Indoor PCB / EEPROM error |
| 2D | Indoor unit fan motor lock / overload (model dependent) |
| 31 | Outdoor unit inverter error |
| 32 | Outdoor unit serial communication error |
| 33 | Outdoor unit capacity / combination error |
| 34 | Discharge temperature sensor error |
| 35 | Outdoor heat exchanger temperature sensor error |
| 36 | Outdoor temperature sensor error |
| 37 | Suction gas temperature sensor error |
| 38 | Expansion valve temperature sensor error (model dependent) |
| 71 | Discharge temperature sensor error |
| 72 | Compressor temperature sensor error |
| 73 | Outdoor heat exchanger liquid temperature sensor error |
| 74 | Outdoor temperature sensor error |
| 75 | Suction gas temperature sensor error |
| 76 | 2-way / 3-way valve temperature sensor error |
| 77 | Heat sink temperature sensor error |
| 82 | Sub-cool heat exchanger sensor error |
| 83 | Liquid pipe temperature sensor error |
| 84 | Current sensor error |
| 86 | Pressure sensor / high pressure switch error |
| 94 | Trip detection |
| 95 | Compressor rotor position detection error (permanent stop) |
| 97 | Outdoor unit fan motor 1 error |
| 98 | Outdoor unit fan motor 2 error |
| 99 | 4-way valve error |
| 9A | Expansion valve (coil) error |
| A1 | Discharge temperature error |
| A3 | Compressor temperature error |
| A4 | High pressure error |
| A5 | Low pressure error |
| AC | Heat sink temperature error |
| J2 | Branch boxes error (system dependent) |
15) UTY-RNRT specific error displays
These error displays are specific to UTY-RNRT wired remote controller system conditions (in addition to the consolidated system error code table above). Use the controller Status → Error Information screen to view error code and the affected address.
| Display | Description (summary) |
|---|
| CC.1 | Sensor error |
| C2.1 | Transmission PCB error |
| 12.1 | Wired remote controller communication error |
| 12.3 | Number excess of device in wired remote controller system |
| 12.4 | Wired remote controller system start-up error |
| 15.4 | Data acquisition error |
| 26.4 | Address duplication in wired remote controller system |
| 26.5 | Address setting error in wired remote controller system |
End of consolidated installation and commissioning solution.