Applies to (as covered by attached manuals):
Indoor (Ducted): ARTH18KMTAP / ARTH24KMTAP / ARTH30KMTAP / ARTH36KMTAP / ARTH45KMTAP / ARTH54KMTAP
Outdoor (Single type): AOTH30KBTA / AOTH36KBTA / AOTH45KBTA / AOTH54KBTA
Outdoor (Single type): AOTH24KCTA / AOTH30KCTA
Wall Controller (Wired): UTY-RNRT (UI / error-display guidance aligned to UTY-RNR family)
Optional parts referenced: Air filter kit UTD-LFDA / UTD-LFDB
Refrigerant: R32
Audience: Authorised service personnel / professional installers


Contents


1) Safety and compliance

  • Installation, electrical work, and commissioning must be performed by qualified and experienced personnel in accordance with applicable standards and local regulations.
  • Do not energise the system until all installation work is complete, covers are fitted, and terminals are verified correct and secure.
  • After isolating power, wait for component discharge before touching electrical parts.
  • If refrigerant leakage occurs during works: ventilate immediately, remove ignition sources, and implement spill/leak response procedures suitable for A2L refrigerants.
  • Use vacuum pump evacuation; do not purge with refrigerant.
  • Ensure correct grounding/earthing, appropriate overcurrent protection, and earth leakage protection as required by local regulations.
  • Do not touch aluminium heat exchanger fins; handle equipment to prevent sharp-edge injury and property damage.

2) R32 refrigerant requirements

  • R32 is an A2L refrigerant (mildly flammable). Implement ignition control, adequate ventilation, and leak detection practices consistent with flammable refrigerant requirements.
  • R32 operates at higher pressures than legacy refrigerants. Use only R32/R410A-rated tools, hoses, and materials.
  • Charging port thread for R32/R410A service ports: 1/2–20 UNF.
  • Prevent moisture/foreign matter entering piping; cap/seal pipe ends during storage/handling and between process steps.
  • Leak detection must be suitable for flammable refrigerants; do not use open flame methods.
  • Use approved recovery methods and cylinders for refrigerant removal, relocation, or end-of-life service activities.

3) Tools and materials (R32/R410A rated)

  • High-pressure gauge manifold suitable for R32/R410A
  • R32/R410A charging hoses (compatible seals and pressure rating)
  • Vacuum pump (recommended with check valve) and appropriate adapters
  • Electronic refrigerant scale (for accurate charging by mass)
  • R32/R410A compatible leak detector (A2L suitable)
  • Tube cutter, deburr tool, flare tool suitable for R32/R410A, flare gauge (as required)
  • Torque wrenches for flare nuts, service valves, and caps
  • Nitrogen cylinder + regulator (for pressure testing / strength & tightness test)
  • Insulation (liquid and gas), UV/impact protection where exposed, and sealing putty for penetrations

4) System overview (power, control, commissioning flow)

4.1 Power and control architecture (typical)

  • Outdoor unit: Main supply connected to the outdoor unit disconnect/isolator.
  • Indoor unit: Powered and controlled per model wiring design (verify terminals and interconnect design for the job). Do not connect AC supply to transmission terminals.
  • Wired controller (UTY-RNRT): Connect to indoor controller terminals per indoor wiring diagram. Observe polarity requirements if specified by the indoor unit (many Fujitsu wired controllers are non-polar on the communication pair, however you must follow the indoor unit terminal marking).

4.2 Recommended commissioning workflow (governance flow)

  • Mechanical installation complete (mounting, duct/drain, piping run, insulation)
  • Electrical installation complete (power, interconnect, controller wiring, terminations verified)
  • Pressure test (nitrogen) with outdoor service valves closed
  • Evacuation (vacuum) to required level and hold test
  • Open service valves fully, refit caps to torque
  • Additional charge if piping exceeds pre-charge length
  • Indoor function settings (static pressure / control features)
  • Test run and validation checks
  • Handover and documentation completion

4.3 Controller & service interaction (operational controls)

  • Use controller Status / Error Information to capture fault codes and unit address where applicable.
  • Where outdoor display PCB is fitted, use the display unit buttons to view local settings and error display modes.
  • For group control / multiple controller configurations, ensure addressing and system architecture is confirmed prior to commissioning (avoid duplicated addressing / mis-termination).

5) Refrigerant piping requirements

5.1 Copper pipe material and minimum wall thickness (R32/R410A)

  • Use seamless phosphor deoxidised copper appropriate for R32/R410A applications.
  • Do not reuse existing piping unless it is verified suitable for R32/R410A cleanliness, pressure rating, and condition (best practice: replace).
Outside diameterNominal sizeMinimum thickness (annealed copper)
6.35 mm1/4"0.80 mm
9.52 mm3/8"0.80 mm
12.70 mm1/2"0.80 mm
15.88 mm5/8"1.00 mm
19.05 mm3/4"1.20 mm

5.2 Line sizes (job verification)

  • Verify the correct liquid and gas line sizes on the outdoor/indoor connection specifications for the exact model combination.
  • Always insulate both liquid and gas lines. Increase insulation thickness in high humidity environments to prevent sweating.
  • Protect pipe ends against moisture/dust entry during storage and installation.

5.3 Piping length limits (outdoor unit reference)

  • Minimum piping length: 5 m
  • Maximum height difference (Indoor → Outdoor): 30 m
  • Maximum piping length (by outdoor series):
    • KBTA (AOTH30/36/45/54): 50 m
    • KCTA (AOTH24/30): follow model limits as specified for the KCTA series (installation must comply with the permissible length table for the exact model).

6) Electrical requirements

6.1 Outdoor unit power supply (AOTH)

  • Voltage rating (model dependent): 1Φ 220–240 V (50 Hz) / 3Φ 380–415 V (50 Hz)
  • Operating range: 1Φ 198–264 V / 3Φ 342–457 V
  • Power supply cable (minimum reference):
    • Single phase: Min. 4 mm² (Type 60245 IEC 66), 2 cable + Earth (Ground)
    • Three phase: Min. 2.5 mm² (Type 60245 IEC 57), 4 cable + Earth (Ground)
  • Breaker capacity / Earth leakage breaker (reference set): Select per model nameplate and local code; ensure adequate interrupt capacity and leakage protection as required.
  • Install a disconnect device with a contact gap of at least 3 mm in all poles nearby the units (indoor and outdoor) as required by local regulations.

6.2 Indoor to outdoor connection cable

  • Follow indoor unit wiring diagram for terminal assignments and conductor sizing.
  • Limit voltage drop to less than 2%; increase conductor size if required.
  • Do not connect AC supply to transmission terminals.

6.3 Wired controller (UTY-RNRT) wiring governance

  • Route controller cable separately from mains power to reduce noise pickup and prevent nuisance communication faults.
  • Terminate securely and confirm strain relief and cable protection at entry points.

7) Outdoor unit installation

7.1 Location and mounting

  • Install on a base that can withstand weight and vibration; use anchor bolts and appropriate anti-vibration measures.
  • Maintain required clearances for airflow and service access. Prevent discharge air recirculation.
  • Do not install where combustible gas may accumulate or in corrosive environments.
  • Secure appropriately for local wind/weather conditions.

7.2 Drain considerations (outdoor)

  • Heating operation produces drain water; route to a suitable drain point where applicable.
  • In freezing climates, apply appropriate freeze protection strategies per local best practice.

7.3 Outdoor display unit & buttons (operation / settings / error access)

ButtonFunction
MODE (S134)Switch between Local setting and Error code display.
SELECT (S133)Navigate individual local settings and error displays.
ENTER (S132)Confirm/commit the selected local setting or error display.
EXIT (S131)Return to operation status display.
PUMP DOWN (S130)Start pump down operation (forced recovery sequence).

7.4 Outdoor field settings (typical functions)

  • Low noise mode: Configure via Local setting mode. Select and confirm the Low Noise mode level required for the site conditions.
  • Peak cut: Configure via Local setting mode. Select the appropriate peak cut level where required by the electrical design / demand strategy.
  • Auto restart: Configure as required by the job scope (power recovery behaviour).
  • Governance note: Perform outdoor field settings after the indoor unit has stopped and prior to commissioning validation.

7.5 External input and output (integration readiness)

  • External input can be used for interlocks and control strategies (job specific). Ensure correct signal type and wiring method.
  • External output can be configured for status outputs (operation status, error status, fresh air control, auxiliary heater, etc.) where supported by the indoor unit configuration.

8) Indoor unit installation

8.1 Site selection and serviceability

  • Install in a location that supports the unit mass and minimises vibration transmission.
  • Ensure ducting, filter access, and condensate drain access are serviceable after installation.
  • Ensure appropriate access for electrical service and refrigerant piping connections.

8.2 Ductwork and airflow management (critical)

  • Confirm ductwork design external static pressure (ESP) aligns with unit capability and commissioning method.
  • Seal duct joints to prevent air leakage and performance degradation.
  • Confirm return air path and filter arrangement prevents debris ingress to the fan/coil.

8.3 Condensate drain

  • Provide correct fall and trapping per local best practice to prevent blow-off and odours.
  • Insulate condensate line where sweating may occur.
  • Water-test drainage prior to ceiling closure / handover.

8.4 Optional part reference – Air filter kit (UTD-LFDA / UTD-LFDB)

  • Bundle the two air filters together with the supplied cable tie (medium). The side bound with the cable tie is the bottom; the side with “PUSH” markings is the front.
  • Fit each air filter to the 4 hooks on the indoor unit.
  • After installation, configure the filter sign function setting as required (see Section 11).

9) Pressure test, evacuation, commissioning

9.1 Flare work – tightening torques (system)

Pipe sizeOutside diameterFlare nut tightening torque
1/4"6.35 mm16–18 N·m
3/8"9.52 mm32–42 N·m
1/2"12.70 mm49–61 N·m
5/8"15.88 mm63–75 N·m
3/4"19.05 mm90–110 N·m

9.2 Leak test (air tightness test)

  • Perform an air tightness test using nitrogen while all outdoor unit valves are closed.
  • Use a test pressure suitable for the equipment and do not exceed the value specified on the outdoor unit nameplate.
  • Confirm all joints are leak-free prior to evacuation.

9.3 Vacuum evacuation

  • Evacuate to –0.1 MPa (–76 cmHg).
  • When –0.1 MPa is reached, operate the vacuum pump for at least 60 minutes.
  • Perform a vacuum hold test to confirm no moisture/air ingress (pressure rise indicates leak or moisture).

9.4 Service valve / port cap torques (outdoor reference)

Cap / PortApplicable sizesTightening torque
Blank cap1/4", 3/8"20–25 N·m
Blank cap1/2"28–32 N·m
Blank cap5/8"30–35 N·m
Blank cap3/4"35–40 N·m
Charging port capR32/R410A12.5–16 N·m

9.5 Final commissioning checks

  • Open service valves fully after evacuation and before starting operation.
  • Confirm correct power supply, correct interconnect wiring, correct controller wiring, and secure terminals.
  • Confirm drainage is normal (water test) and insulation complete.
  • Confirm no refrigerant leakage using an A2L compatible electronic leak detector.

10) Additional refrigerant charging

  • Pre-charge length: 30 m
  • If piping length exceeds 30 m, additional refrigerant is required.
  • Charging guideline: 40 g/m beyond 30 m.
  • Calculation: Additional charge (g) = (Actual piping length (m) – 30) × 40, for lengths > 30 m.
  • Record factory (base) charge, additional charge, and total charge on the outdoor unit refrigerant label.

10.1 KBTA (AOTH30/36/45/54)

Piping lengthAdditional chargeGuideline
≤ 30 mNone40 g/m beyond 30 m
40 m+400 g
50 m+800 g

10.2 KCTA (AOTH24/30)

Piping lengthAdditional chargeGuideline
≤ 30 mNone40 g/m beyond 30 m
40 m+400 g
50 m+800 g
60 m+1200 g
70 m+1600 g
75 m+1800 g

11) Indoor function settings

11.1 Governance notes

  • Function settings change indoor unit control behaviour. Incorrect settings can cause malfunction, noise, water leakage, or comfort issues.
  • After completing Function Setting, turn power off and back on to apply the settings.
  • Record all changes in job documentation for service governance.

11.2 Setting record (functions used in this series)

  • Function numbers commonly used for this ducted series include: 11 (Filter sign), 26 (Static pressure), 30/31 (Room temp control – indoor sensor cooling/heating), 35/36 (Room temp control – wired controller sensor cooling/heating), 40 (Auto restart), 42 (Room temp sensor switching), 43 (Cold air prevention), 46 (External input control), 48 (Room temp sensor switching (Aux.)), 49 (Indoor fan control for energy saving for cooling), 60 (External output function switching).

11.3 Static pressure setting (Function No. 26) – commissioning control

  • Manual setting: Select the required Pa value where duct ESP is known.
  • Automatic airflow adjustment: Use when commissioning requires automated fan calibration (ensure system complete and stable before initiation; not suitable where a booster fan is installed between ducts).
Function No.Setting valueStatic pressure / mode
260550 Pa
260660 Pa
260770 Pa
260880 Pa
260990 Pa
2610100 Pa
2611110 Pa
2612120 Pa
2613130 Pa
2614140 Pa
2615150 Pa
2632Automatic airflow adjustment

11.4 Indoor fan control for energy saving for cooling (Function No. 49)

Function No.Setting valueDescription
4900Disable – when outdoor unit is stopped, indoor fan operates continuously following remote controller setting.
4901Enable – when outdoor unit is stopped, indoor fan operates intermittently at very low speed.
4902Remote controller – enable/disable via remote controller setting (if supported by controller type).

11.5 External output function switching (Function No. 60)

Function No.Setting valueOutput function
6000Operation status
6009Error status
6010Fresh air control
6011Auxiliary heater

12) Test run and handover

12.1 Pre-test run check items

  • Controller operation and display status normal
  • Indoor fan operation stable (no hunting / abnormal ramping)
  • Airflow achieved and duct system balanced
  • Drainage normal (no water leakage)
  • No abnormal noise or vibration
  • No refrigerant leakage detected

12.2 Customer guidance (handover governance)

  • Explain controller operation, setpoints, timers/schedules (where applicable).
  • Explain filter access/cleaning intervals and service requirements.
  • Confirm any building management interface / external interlocks (if installed).
  • Provide commissioning records, wiring schematics as installed, and refrigerant charge documentation.

13) Pump down (forced cooling operation)

  • Use pump down for relocation/disposal refrigerant recovery in accordance with manufacturer procedure and local regulatory requirements.
  • Initiate forced cooling / test run mode per controller guidance (method varies by controller type).
  • Close the 2-way valve fully, then close the 3-way valve after the required run period, then stop operation.
  • Do not proceed if refrigerant is depleted due to damaged piping; confirm leak-free condition first.
  • Use the outdoor display unit PUMP DOWN button where provided to start the pump down operation sequence.

14) Error codes (indoor/outdoor consolidated)

Error codes may be displayed on the wired controller, or indicated via outdoor display unit error mode where fitted. Capture the code, confirm wiring/communication integrity, and follow standard diagnostic workflow (power, comms, sensors, loads, then control PCB).

Error codeDescription (summary)
11Serial communication error
12Wired remote controller communication error
15Check run unfinished / automatic airflow adjustment error
16Peripheral unit transmission PCB connection error
18External communication error
21Unit number / address setting error (system dependent)
22Indoor unit capacity / combination error (system dependent)
23Communication circuit error (system dependent)
24Indoor fan motor error
25Drain / float switch error
26Indoor heat exchanger temperature sensor error
27Indoor room temperature sensor error
28Indoor coil inlet / outlet sensor error (model dependent)
29Indoor discharge air temperature sensor error (model dependent)
2AOutdoor unit combination error (system dependent)
2CIndoor PCB / EEPROM error
2DIndoor unit fan motor lock / overload (model dependent)
31Outdoor unit inverter error
32Outdoor unit serial communication error
33Outdoor unit capacity / combination error
34Discharge temperature sensor error
35Outdoor heat exchanger temperature sensor error
36Outdoor temperature sensor error
37Suction gas temperature sensor error
38Expansion valve temperature sensor error (model dependent)
71Discharge temperature sensor error
72Compressor temperature sensor error
73Outdoor heat exchanger liquid temperature sensor error
74Outdoor temperature sensor error
75Suction gas temperature sensor error
762-way / 3-way valve temperature sensor error
77Heat sink temperature sensor error
82Sub-cool heat exchanger sensor error
83Liquid pipe temperature sensor error
84Current sensor error
86Pressure sensor / high pressure switch error
94Trip detection
95Compressor rotor position detection error (permanent stop)
97Outdoor unit fan motor 1 error
98Outdoor unit fan motor 2 error
994-way valve error
9AExpansion valve (coil) error
A1Discharge temperature error
A3Compressor temperature error
A4High pressure error
A5Low pressure error
ACHeat sink temperature error
J2Branch boxes error (system dependent)

15) UTY-RNRT specific error displays

These error displays are specific to UTY-RNRT wired remote controller system conditions (in addition to the consolidated system error code table above). Use the controller StatusError Information screen to view error code and the affected address.

DisplayDescription (summary)
CC.1Sensor error
C2.1Transmission PCB error
12.1Wired remote controller communication error
12.3Number excess of device in wired remote controller system
12.4Wired remote controller system start-up error
15.4Data acquisition error
26.4Address duplication in wired remote controller system
26.5Address setting error in wired remote controller system

End of consolidated installation and commissioning solution.